R-ISM guide rail OPP.HI.SIDE TS 5000 With closing sequence control, electrical hold-open device on both leaves, smoke switch control unit and levers
- Integrated electric hold-open device
- Retention force of the electromechanical hold-open device can be variably adjusted
- Integrated smoke switch control unit
- Smoke switch with contamination indicator and adaption of the alarm threshold
- Additional smoke detectors can be fitted
- Operating voltage 230 V AC
- Closing sequence control holds the active leaf in the waiting position until the passive leaf is closed
- With screwed slide block
- Horizontally adjustable in the installation position by 4 mm through elongated holes
Application Areas
- Double leaf doors with closing sequence control
- Hold-open systems with integrated hold-open device and smoke switch
- Installation on the opposite hinge side
- Right and left single-action doors
- Symmetrical and asymmetrical division of door possible
- Up to 2800 mm hinge clearance
- Minimum hinge clearance 1560 mm, minimum width of the active leaf 905 mm and of the passive leaf 380 mm
Technical data
| R-ISM guide rail OPP.HI.SIDE TS 5000 | |
| Supply voltage | 230 V AC |
| Input voltage | 230 V AC |
| Frequency of supply voltage | 50/60 Hz |
| Duty rating | 100 % |
| IP rating | IP20 |
| Minimum hinge clearance | 1560 mm |
| Minimum passive leaf width | 380 mm |
| Standard conformity | EN 1155, EN 1158 |
| Approvals | General building approval from DIBt as a hold-open system |
| Length | 2730 mm |
| Width | 55 mm |
| Height | 30 mm |
| opening restrictor upgradable | Yes |
| Hold-open function | Electrical |
| Hold-open device can be overridden | Yes |
| Hold-open range | 80 ° - 130 ° |
| Smoke switch integrated | Yes |
| Contamination indicator | Yes |
| Adaption of the alarm threshold | Yes |
| Integrated power supply | Yes |
| Closing sequence control integrated | Yes |
| Height correction possible | Yes |
| Flexible opening restrictor | Yes |
Downloads